Create Free Business AccountThe 1182W12 is a 1000 VA toroidal power transformer from the 1182 Series for equipment designers who need a high-current 12 V or 24 V centre-tapped AC source. It runs from a dual 117/234 VAC primary at 50/60 Hz and carries two 12 V secondaries rated 41.70 A each.
With the secondaries in series the output is 24V C.T. @ 41.7A; in parallel it is 12V @ 83.4A. The series table lists voltage regulation at 2.20%. The units are designed to have all windings engaged, either series or parallel connected, or connected as an autotransformer, and a connection sheet is included with the transformer.
This is an open-center toroid (dimension reference L-1). It is supplied with two 0.093" T x 4.75" OD rubber washers, one 16GA x 4.30" OD steel mounting washer, and one 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut. Primary leads are #16 TEW and secondary leads are #10 TEW, all brought out 8"-9" and stripped 0.5" minimum. The drawing gives a weight of 16.29 lbs +/- 4%, with a shipping weight of 16.5 lbs (7.48 kg).
The toroid core shape provides a low profile, lightweight, cool running, high efficiency transformer with low stray magnetic flux leakage (low EMI). It uses Class B (130 degree C) materials and is hi-pot tested at 4000V, 60Hz for 1 second primary to secondary and 600V primary to primary and secondary to secondary. The 1182 Series is UL recognized (file #E207860) and CSA certified (file #209651); the 1182W12 is RoHS and REACH compliant. Because toroids draw high inrush current on switch-on, use a slow-blow fuse, time delayed breaker or soft start circuitry.
| Supplied Hardware | Two 0.093" T x 4.75" OD rubber washers; one 16GA x 4.30" OD steel mounting washer; one 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut |
| Series Hardware Note | Two neoprene rubber insulating pads, one metal centering washer and all mounting hardware |
| Series | 1182 Series |
| Replaces | Older 182 Toroid Series |
| Power Rating | 1000 VA |
| Product Type | Power transformer, toroid |
| Toroid Center | Open |
| Short Description | TOROID,1000VA, 50/60HZ, 12/12V |
| Dimension Reference | L-1 |
| Included Documentation | Connection sheet included with transformer |
| Primary | Dual 117/234 VAC primary, 50/60 Hz operation |
| Polarity | BLK, BRN, RED and GRY additive |
| Inrush Note | High magnetizing current when initially energized; consider a slow-blow fuse, time delayed circuit breaker or soft start circuitry |
| Primary Windings | 2x 117V 50/60Hz (BLK-WHT, BRN-ORN) |
| Secondary Windings | 2x 12V @ 41.70A (RED-BLU, GRY-YEL) |
| Winding Connection | All windings engaged (series or parallel connected) or connected as an autotransformer |
| Secondary (RMS) Series | 24V C.T. @ 41.7A |
| Dual Or Single Secondary | Dual |
| Hi-Pot Primary - Primary | 600V, 60Hz, 1 sec |
| Secondary (RMS) Parallel | 12V @ 83.4A |
| Hi-Pot Test (Series Spec) | 4,000 VAC RMS between primary & secondary |
| Hi-Pot Primary - Secondary | 4000V, 60Hz, 1 sec |
| Hi-Pot Secondary - Secondary | 600V, 60Hz, 1 sec |
| % Voltage Regulation (Part Page) | 2 |
| % Voltage Regulation (Series Table) | 2.20% |
| Secondary No-Load Voltage Test Conditions | @ 117V, 60Hz BLK & BRN to WHT & ORN, or @ 234V, 50Hz BLK to ORN (connect BRN & WHT) |
| UPC | 623980240428 |
| UNSPSC | 39121301 |
| Label Code | 1A1000A000C012012 |
| Country Of Origin | Made in Canada |
| Shipping Weight | 16.5 lbs (7.48 kg) |
| Weight (Drawing) | 16.29 lbs +/- 4% |
| Core Type | Toroid |
| Lead Length | All leads out 8"-9" and stripped 0.5" min |
| Primary Leads | #16 TEW |
| Secondary Leads | #10 TEW |
| Insulation Class | Class B (130 degree C) materials |
| Leads (Series Spec) | Minimum 8" long flexible leads |
| UL | UL recognized to UL 5085-1 and UL 5085-2, UL file #E207860 |
| CSA | CSA certified to C22.2 #66.1-6 and C22.2 #66.2-6, CSA file #209651 |
| IEC/EN | Self-declared evaluated to applicable sections of IEC/EN61558-1 (Second Edition 2005-09) and IEC/EN61558-2-4 |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Business account holders get access to exclusive pricing, volume discounts, and dedicated support. Create a free account to get started.
Its two 12V @ 41.70A secondaries give 24V C.T. @ 41.7A when connected in series, or 12V @ 83.4A when connected in parallel.
Yes. The dual 117V primaries are wired in parallel for 117 VAC or in series for 234 VAC, at 50/60 Hz.
Two 0.093" T x 4.75" OD rubber washers, one 16GA x 4.30" OD steel mounting washer, and one 3/8-16 bolt 3.50" long with a lock washer and 3/8-16 hex nut.
Primary leads are #16 TEW and secondary leads are #10 TEW. All leads come out 8"-9" and are stripped 0.5" minimum.
The 1182 Series ordering table lists 2.20% voltage regulation for the 1182W12.
Toroidal transformers can draw high magnetizing current at switch-on for up to about half a cycle, so a slow-blow fuse, time delayed circuit breaker or soft start circuitry is recommended.
Save 50%Hammond Manufacturing · 101D
Save 50%Hammond Manufacturing · 101F
Save 50%Hammond Manufacturing · 101H
Save 50%Hammond Manufacturing · 101J
Save 50%Hammond Manufacturing · 101P