The SKT011409NC is a normally closed (NC) enclosure thermostat with a Fahrenheit scale, from the SKT Series. It provides air temperature control and monitoring in cabinets and is the version used with heaters and heater fans: its contact opens when rising temperature reaches the set point, shutting the heater off. Electricians and panel builders use it to automate enclosure heating instead of leaving heaters powered continuously.
A thermostatic bi-metal sensor drives a snap-action contact, adjustable from 30 to 140°F (0 to 60°C). The switching difference (hysteresis) is + or - 4°F (+ or - 3 K), and the NC setting knob carries a red imprint. The switching capacity is 15A @ 120VAC, 10A @ 240VAC, and 30W @ DC, and noise suppression is class N according to VDE 0875.
The ordering table gives dimensions of 2.8 x 1.5 x 1.4 (height x width x depth); the short description lists 2.41 x 1.3 x 1.4 in. The housing is flame retardant UL94V0 plastic in gray, protected to IP20, with a 2 pole terminal for AWG 14 (2.5 mm²) wire. The thermostat clips onto 35 or 38 mm DIN rail with the included clip.
The instructions call for installation by qualified staff, in the upper part of the cabinet as far as possible from heat-creating components, without covering the ventilation slots. When setting an NC thermostat, add the highest possible hysteresis to the required minimum temperature. The SKT011409NC is UL Recognized Component, cUL Recognized Component and CE approved, RoHS and REACH compliant, and ships at 0.2 lb (0.09 kg).
| Scale | F° |
| Series | SKT Series Thermostats |
| Contact Type | Normally Closed (contact opens with rising temperature) |
| Product Type | Norm. Closed Thermostat Fahrenheit |
| Setting Knob | Red imprint (NC) |
| Sensor Element | Thermostatic bi-metal |
| Adjustment Range | 30 - 140°F / 0 - 60°C |
| Short Description | THERMOSTAT 2.41X1.3X1.4" |
| Tolerance For Switching Point | +/- 4 K |
| Switching Difference (Hysteresis) | + or - 4°F (+ or - 3 K); instruction sheet: temperature difference < 7 K |
| Size (Short Description) | 2.41 x 1.3 x 1.4 in |
| Height X Width X Depth (Ordering Table) | 2.8 x 1.5 x 1.4 |
| Connection | 2 pole terminal for AWG 14 (2.5 mm²) |
| Contact Design | Snap-action contact |
| Noise Suppression | N (according to VDE 0875) |
| Switching Capacity | 15A @ 120VAC, 10A @ 240VAC, 30W @ DC |
| Max. Breaking Capacity (Instruction Sheet) | 240V AC, 10 (2)A / 120V AC, 15 (2)A; DC max. 30W (value in brackets: inductive load at cos φ = 0.6) |
| UPC | 623980565194 |
| UNSPSC | 41112209 |
| Mounting | Clip mounting on 35 or 38 mm DIN rail (clip included) |
| Shipping Weight | 0.2 lbs (0.09 kg) |
| Color | Gray (SB) |
| Housing | Flame retardant plastic UL94V0 |
| Protection | IP20 |
| Working Temperature Range (Instruction Sheet) | -20°C .. +80°C / -5°F .. +180°F |
| Approvals | UL Recognized Component, cUL Recognized Component, CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
It is the normally closed version, used with heaters and heater fans. The contact opens when rising temperature reaches the set point, shutting the heater off.
30 - 140°F / 0 - 60°C, on a Fahrenheit scale.
15A @ 120VAC, 10A @ 240VAC, and 30W @ DC.
In the upper part of the switch cabinet at the maximum possible distance from heat-creating components, without covering its ventilation slots.
Add the highest possible hysteresis to the required minimum temperature. The instruction example sets 20°C (66°F) for a required minimum of 9°C (46°F), adding 11 K (7 K + 4 K).
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021
Hammond Manufacturing · 012000055