The SKT011409NC-C is the Celsius-scale version of the SKT Series normally closed (NC) thermostat. It provides air temperature control and monitoring in electrical cabinets and is intended for heaters and heater fans: its contact opens when rising temperature reaches the set point, shutting the heater off. It suits panel builders and OEMs working to metric specifications.
The sensing element is a thermostatic bi-metal driving a snap-action contact, with an adjustment range of 0 to 60°C (30 to 140°F) and a switching difference of + or - 3 K (+ or - 4°F). The NC setting knob has a red imprint. Switching capacity is 15A @ 120VAC, 10A @ 240VAC and 30W @ DC, and noise suppression is N according to VDE 0875.
Dimensions in the ordering table are 2.8 x 1.5 x 1.4 (height x width x depth). The housing is flame retardant plastic rated UL94V0, colored gray, with IP20 protection. A 2 pole terminal accepts AWG 14 (2.5 mm²) wire, and the unit clips onto 35 or 38 mm DIN rail using the included clip.
Per the instructions, it should be installed by qualified staff in the upper part of the cabinet, as far as possible from heat-creating components, with its ventilation slots uncovered. For an NC thermostat, set the dial to the required minimum temperature plus the highest possible hysteresis. The SKT011409NC-C carries UL Recognized Component, cUL Recognized Component and CE approvals, is RoHS and REACH compliant, and has a shipping weight of 0.18 lb (0.08 kg).
| Scale | C° |
| Series | SKT Series Thermostats |
| Contact Type | Normally Closed (contact opens with rising temperature) |
| Product Type | Norm. Closed Thermostat Celsius |
| Setting Knob | Red imprint (NC) |
| Sensor Element | Thermostatic bi-metal |
| Adjustment Range | 30 - 140°F / 0 - 60°C |
| Short Description | THERMOSTAT - CELSIUS SCALE |
| Tolerance For Switching Point | +/- 4 K |
| Switching Difference (Hysteresis) | + or - 4°F (+ or - 3 K); instruction sheet: temperature difference < 7 K |
| Height X Width X Depth (Ordering Table) | 2.8 x 1.5 x 1.4 |
| Connection | 2 pole terminal for AWG 14 (2.5 mm²) |
| Contact Design | Snap-action contact |
| Noise Suppression | N (according to VDE 0875) |
| Switching Capacity | 15A @ 120VAC, 10A @ 240VAC, 30W @ DC |
| Max. Breaking Capacity (Instruction Sheet) | 240V AC, 10 (2)A / 120V AC, 15 (2)A; DC max. 30W (value in brackets: inductive load at cos φ = 0.6) |
| UPC | 623980567815 |
| UNSPSC | 41112209 |
| Mounting | Clip mounting on 35 or 38 mm DIN rail (clip included) |
| Shipping Weight | 0.18 lbs (0.08 kg) |
| Color | Gray (SB) |
| Housing | Flame retardant plastic UL94V0 |
| Protection | IP20 |
| Working Temperature Range (Instruction Sheet) | -20°C .. +80°C / -5°F .. +180°F |
| Approvals | UL Recognized Component, cUL Recognized Component, CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
Both are normally closed thermostats; the -C version uses a Celsius scale, while SKT011409NC uses Fahrenheit.
It is used with heaters. The contact opens when rising temperature reaches the set point, shutting the heater off.
0 - 60°C (30 - 140°F).
A 2 pole terminal for AWG 14 (2.5 mm²).
It clips onto 35 or 38 mm DIN rail; the clip is included.
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021
Hammond Manufacturing · 012000055