PWS7152A230N4LG is the 230 V version of the PWS 7152 air/water heat exchanger, listed as a 5100 BTU/H, NEMA 3R/4 unit in light gray. Engineers use this type of unit to cool enclosures with water rather than ambient air, which matters where the surroundings are hot, harsh or regularly washed down.
For correct operation the cooling liquid must be at least 10 °C colder than the heat exchanger inlet air. Water connections should use flexible pressure-resistant (>10 bar) hose secured with clamps, and the maximum permissible operating pressure is 10 bar. When stored or transported below freezing the water circuit must be emptied with compressed air, and the unit should not be exposed to temperatures above +70 °C.
The PWS7152A230N4LG is installed with the supplied PWS 7332/7152 drilling template; its drawing gives an overall height of 950 mm (37.40 in) and width of 400 mm (15.75 in). The series case is galvanized steel in RAL7035 light gray, and series standards are UL, cUL and CE. Included items are the cooling unit, mounting cutout, manual and technical data sheet. Shipping weight is 55 lbs (24.95 kg); the part is REACH and RoHS compliant, UPC 623980720463.
| Series | PWS 7000 Series Air/Water Heat Exchanger (3000-10000 BTU/H), Type 3R, 4, 4X |
| Application | Uses various water sources to cool enclosures where ambient conditions involve high temperatures, harsh conditions or frequent wash-down |
| Description | AW HX Unit 5100 BTU/H 230 V - NEMA 3R/4 - Lt. Gray |
| Short Description | AIR WATER EXCHANGER 230V |
| Nominal Cooling Capacity | 5100 BTU/H |
| Width (Drawing) | 400 mm (15.75 in) |
| Height (Drawing) | 950 mm (37.40 in) |
| Voltage | 230 V |
| Available Accessories | Remote door switches, gasket kits, condensate bottle |
| UPC | 623980720463 |
| UNSPSC | 40101802 |
| Part Number | PWS7152A230N4LG |
| Design | Low noise, maintenance-free |
| Heat Exchanger | Rugged (10 bar) copper tube / aluminum fin |
| Water Connection | 1/2" barb connection |
| Compatible Coolants | Chilled water/glycol, tower water and other circulated coolants |
| Temperature Control | Integrated thermostat & solenoid valve with alarm contact for automatic temperature control |
| Coolant Temperature Requirement | Cooling liquid must be at least 10 °C colder than the heat exchanger inlet air temperature |
| Water Hose | Flexible pressure-resistant (>10 bar) hose, secured with clamps |
| Mounting Options | Side, door or internal mounting |
| Drilling Template | PWS 7332/7152 drilling template (supplied) |
| Included Items | Cooling unit, mounting cutout, manual, technical data sheet |
| Shipping Weight | 55 lbs (24.95 kg) |
| Accessory Pack (Typical) | Sealing strips, threaded mounting studs, mounting bolts, nuts and washers, condensate hose, door contact connector/jumper |
| Color | Lt. Gray |
| Exterior Case (Series) | Galvanized steel construction, finish RAL7035 Light Gray |
| Storage | Not to be exposed to temperatures exceeding +70 °C; water circuit must be emptied with compressed air if stored or transported below freezing |
| Enclosure Rating (Part) | NEMA 3R/4 |
| Max. Permissible Operating Pressure | 10 bar |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| Series Standards | UL, cUL, and CE |
| Series Compliance | Complies with NEMA 3R, 4, 4X |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
It is the 230 V version of the 5100 BTU/H PWS 7152 unit.
The included items are the cooling unit, mounting cutout, manual and technical data sheet; the accessory pack typically adds sealing strips, threaded mounting studs, mounting bolts, nuts and washers, a condensate hose and a door contact connector/jumper.
The maximum permissible operating pressure is 10 bar.
If stored or transported below freezing, the water circuit must be completely emptied using compressed air.