The PWS3062A230N4LG is a compact air/water heat exchanger from the PWS 3000 Series: the smallest-capacity model in the 2000-3000 BTU/H PWS 3000 range. Panel builders and OEM designers use it to cool enclosures with chilled water/glycol, tower water or other circulated coolants where ambient conditions are hot, harsh or subject to frequent wash-down.
Rated at 2216 BTU/h (650 W) with the enclosure at +95 F (+35 C) and water at +50 F (+10 C), the PWS 3062 moves 100 CFM (170 m3/h) of internal air across the coil and needs 2 GPM (450 L/h) of coolant at its rated capacity. This is the 230 V version, specified for 50/60 Hz supply; it consumes 30.4 W and draws 0.15 A running current, with a terminal block power connection. An integrated thermostat and solenoid valve with alarm contact provide automatic temperature control.
The exterior case is galvanized steel finished in RAL7035 Light Gray (LG), and the series complies with NEMA 3R, 4, 4X. Inside, a rugged (10 bar) copper tube / aluminum fin heat exchanger connects through a 1/2 in barb. The series ordering table gives the unit as 24.10 in (612 mm) high, 10.13 in (257 mm) wide and 5.62 in (143 mm) deep. Shipping weight is 20 lbs (9.07 kg). The series is rated UL, cUL and CE.
Its technical companion sheet adds a 100 % duty cycle, noise under 51 dB at 1 m, vertical installation and a 45 C alarm on an NC contact (5 A maximum input). Note that the part description for PWS3062A230N4LG shows 1000 W, while the series specification sheet rates the PWS 3062 model at 2216 BTU/h (650 W). Side, door or internal mounting gives installation flexibility, and the low noise design is maintenance-free. The manual requires coolant at least 10 C colder than the inlet air.
| Leak Testing | All devices are checked for leaks before leaving the factory |
| Model | PWS 3062 |
| Series | PWS 3000 Series (2000-3000 BTU/H) |
| Product Type | Air/Water Heat Exchanger |
| Long Description | Air/Water Heat Exch. 1000W 230V LG |
| Short Description | AIR WATER EXCHANGER 1000W/230V |
| Rating Shown In Part Description | 1000 W |
| Depth (Series Table) | 5.62 in (143 mm) |
| Width (Series Table) | 10.13 in (257 mm) |
| Height (Series Table) | 24.10 in (612 mm) |
| Weight Without Packaging | 10 kg (22 lb) |
| Height X Width X Depth (Technical Sheet) | 613 x 257 x 143 mm (24.14 x 10.13 x 5.62 in) |
| Frequency | 50/60 Hz |
| Pre-Fuse T | .5 A gG |
| Running Amps | 0.15 A |
| Rated Voltage | 230 V |
| Power Connection | Terminal Block (hard wired terminal) |
| Starting Current | .16 A |
| Power Consumption | 30.4 W |
| Alarm Switch Setting | 45 C |
| Temperature Monitoring (Alarm) | NC contact; maximum input 5 A |
| Available Accessories | Remote door switches, gasket kits, condensate bottle |
| Condensate Discharge | 1/2 in OD hose barb |
| Heat Exchanger Connection | 1/2 in barb connection |
| Cooling Water Connection (Technical Sheet) | 1/2 in push-in fitting |
| UPC | 623980720531 |
| UNSPSC | 39121301 |
| Part Number | PWS3062A230N4LG |
| Door Contact | Door contact switch recommended to turn the unit off when the enclosure door is opened |
| Mounting Style | Bolt-on unit for door or side mounting on electrical panel enclosures |
| Mounting Options | Side, door or internal mounting |
| Cooling Water Hose | Flexible pressure-resistant (>10 bar) hose secured with clamps |
| Installation Attitude | Vertical |
| Supply Voltage Tolerance | Within ± 10% of the ID plate value |
| Supply Frequency Tolerance | Within ± 3 Hz of the ID plate value |
| Insulation Strip Compression | 2 mm (approx. 0.080 in) |
| Coolant Temperature Requirement | Cooling liquid must be at least 10 C colder than the heat exchanger inlet air temperature |
| Maximum Permissible Operating Pressure | 10 bar |
| Fan Spare Part No. | 18611000016 |
| Solenoid Valve (230V) Spare Part No. | 18785000004 |
| (Electronic) Controller (230V) Spare Part No. | 18783000006 |
| (Mechanical) Thermostat (115/230V) Spare Part No. | 18713000001 |
| Temperature Sensor (Eliwell Controller Units Only) Spare Part No. | 18783000007 |
| Coolant | Water |
| Air Volume | 100 CFM (170 m3/h) |
| Duty Cycle | 100 % |
| Factory Setting | +95 F (+35 C) |
| Operating Pressure | 14.5 - 145 PSI (1 - 10 bar) |
| Compatible Coolants | Chilled water/glycol, tower water and other circulated coolants |
| Temperature Control | Integrated thermostat and solenoid valve with alarm contact for automatic temperature control |
| Water Inlet Temperature | 10 C (>+1 C to +35 C) / 50 F (>+34 F to +95 F) |
| Adjustable Control Range | +50 to +104 F (+10 to +50 C) |
| Thermostat Factory Setting | +35 C / 95 F |
| Flow Rate At Rated Capacity | 2 GPM (450 L/h) |
| Range Of Adjustment (Technical Sheet) | min. 10 C / 50 F - max. 40 C / 104 F |
| Cooling Capacity Test Point (Technical Sheet) | L35 / W10 / 454 l/h |
| Cooling Capacity (Enclosure +95 F / +35 C, Water +50 F / +10 C) | 2216 BTU/h (650 W) |
| Included Items | Cooling unit, mounting cutout, manual, technical data sheet |
| Shipping Weight | 20 lbs (9.07 kg) |
| Accessory Pack (Typical) | Sealing strips, threaded mounting studs, mounting bolts, nuts and washers, condensate hose, door contact connector/jumper |
| Design | Low noise, maintenance-free |
| Finish | RAL7035 Light Gray |
| Exterior Case | Galvanized steel |
| Unit Construction | Steel |
| Heat Exchanger Core | Rugged (10 bar) copper tube / aluminum fin |
| Corrosion Protection | Galvanized, electrostatically powder coated (200 C) - stainless steel |
| Noise Level (1 M) | < 51 dB |
| Freezing Conditions | Water circuit must be completely emptied with compressed air before storage or transport below freezing |
| Ambient Air Temperature | +36 to +140 F (+2 to +55 C) |
| Storage Temperature Limit | Must not be exposed to temperatures exceeding +70 C |
| Enclosure Internal Temperature | +25 C / 77 F to +45 C / 113 F |
| Standards | UL, cUL, and CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| Series Enclosure Ratings | NEMA 3R, 4, 4X |
| Protective Category (UL, Technical Sheet) | Type 12 / 3R / 4 (4X stainless steel only) |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
The series specification sheet rates the PWS 3062 at 2216 BTU/h (650 W) with the enclosure at +95 F (+35 C) and the water at +50 F (+10 C). The part description itself shows 1000 W.
This variant is rated 230 V at 50/60 Hz, consumes 30.4 W and draws 0.15 A running current. Power connects through a terminal block. Supply voltage must be within ± 10% and frequency within ± 3 Hz of the ID plate values.
It is compatible with chilled water/glycol, tower water and other circulated coolants. Rated capacity needs 2 GPM (450 L/h), operating pressure is 14.5 - 145 PSI (1 - 10 bar), and the coolant must be at least 10 C colder than the heat exchanger inlet air.
The series supports side, door or internal mounting. The manual describes bolting the unit to the enclosure with the supplied stud bolts, screws and washers, compressing the insulation strips to 2 mm (approx. 0.080 in).
The exterior case is galvanized steel finished in RAL7035 Light Gray, and the series complies with NEMA 3R, 4, 4X. The series lists UL, cUL and CE.
The series specification sheet lists remote door switches, gasket kits and a condensate bottle as accessories. A door contact switch is recommended to turn the unit off when the enclosure door is opened.
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021
Hammond Manufacturing · 012000055