The PKS3303A460N4LG is a Type 3R/4 closed loop air to air heat exchanger from the PKS4 Series, rated 150 W/°C (83 W/°F) and powered from a 400/460V supply at 50 or 60 Hz. It is the third capacity step in the series, designed for outdoor applications and suited to outdoor switch cabinets that must keep their NEMA 3R/4 rating.
An air to air heat exchanger is a fit when the surrounding air is at least 10°C/18°F cooler than the target internal temperature. Clean enclosure air is recirculated in a closed loop and never mixes with contaminated ambient air, and the series is described as more energy efficient with lower maintenance costs than air conditioners. At a 20°C/36°F difference between ambient and target internal temperature, the PKS3303A460N4LG shows a sample performance of 3000W (10200 BTU); actual cooling depends on that ΔT.
The ordering table gives 35.30 in (897 mm) high, 11.97 in (304 mm) wide and 16.04 in (407 mm) deep including louvers, which extend 1.5 in on either side (nominal size 35 in x 12 in x 16 in (889 mm x 305 mm x 406 mm)). Shipping weight is 65 lbs (29.48 kg). The cover is finished in Light Gray (RAL7035) powder coated steel. The unit maintains the enclosure's NEMA 3R/4 rating, is rated IP 56 and carries UR, cUR and CE marks, uses R134a refrigerant, and its EMI/RFI suppression meets CE.
For installation, a gasket, mounting kit and template for the cutout and drilling are included, and the unit can be mounted vertically or horizontally. The thermostat control is accessible from inside the enclosure, and a door contact provision powers the unit down when the enclosure door is opened. Remote door switches and gasket kits are available as accessories.
| Series | PKS4 Series (Air to Air Heat Exchangers - Type 3R/4) |
| Designed For | Outdoor applications |
| Product Type | Air to Air Heat Exchanger |
| Cooling Principle | Closed loop; clean enclosure air is recirculated without mixing with contaminated ambient air |
| Short Description | AA HX 150W/C 460V N4 LT GRAY |
| Application Condition | Surrounding air temperature lower than target internal temperature by at least 10°C/18°F |
| Depth | 16.04 in (407 mm) |
| Width | 11.97 in (304 mm) |
| Height | 35.30 in (897 mm) |
| Louvers | Extend 1.5 in on either side |
| Nominal Size (H X W X D) | 35 in x 12 in x 16 in (889 mm x 305 mm x 406 mm) |
| Overall Dimensions (Drawing) | 897 mm (35.31 in) H x 304 mm (11.97 in) W x 407 mm (16.04 in) D |
| Additional Drawing Depth Dimensions | 370 mm (14.57 in); 271 mm (10.65 in) |
| Door Contact | Provision for power down when enclosure door is opened |
| EMI/RFI Suppression | Meets CE |
| Temperature Control | Thermostat control accessible from inside enclosure |
| Voltage - Frequency | 400/460V 50/60 Hz |
| Controller Set Points | Unit set point control (1TAS) and alarm set point control (2TAS) |
| UPC | 623980273242 |
| UNSPSC | 39121301 |
| Part Number | PKS3303A460N4LG |
| Refrigerant | R134a |
| Performance Note | Actual cooling performance based on difference (ΔT) between ambient and target internal temperature |
| Cooling Capacity (W/°C) | 150 W/°C |
| Cooling Capacity (W/°F) | 83 W/°F |
| Sample Performance At ΔT = 20°C/36°F | 3000W (10200 BTU) |
| Included | Gasket, mounting kit and template for cutout and drilling |
| Operation | Stationary operation only |
| Scope Of Delivery | Cooling unit, quick guide, accessory kit (seal, fastening material, electrical plug connector, etc.), special accessories if applicable |
| Mounting Orientation | Vertical or horizontal |
| Available Accessories | Remote Door Switches; Gasket Kits |
| Drilling Template Mounting Holes | 14 x 8 mm (0.31 in) |
| Shipping Weight | 65 lbs (29.48 kg) |
| Cover | Light Gray (RAL7035) powder coated steel |
| Ingress Protection | IP 56 |
| Enclosure Rating Maintained | NEMA 3R/4 |
| Approvals | UR, cUR and CE |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| Material Declaration | Free from silicone connections; PCT, asbestos, formaldehyde, cadmium; moisture-impairing substances |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
It is rated 150 W/°C (83 W/°F). As a sample, at a 20°C/36°F difference between ambient and target internal temperature it delivers 3000W (10200 BTU). Actual performance depends on that temperature difference.
The ordering table lists 400/460V 50/60 Hz for this part number. Other voltages are offered as separate part numbers in the PKS4 Series.
When the surrounding air temperature is lower than the target internal temperature by at least 10°C/18°F. The closed loop recirculates clean enclosure air without mixing it with contaminated ambient air.
Yes. The PKS4 Series maintains the enclosure's NEMA 3R/4 rating, is rated IP 56 and carries UR, cUR and CE marks.
A gasket, mounting kit and template for the cutout and drilling are included, along with a quick guide and an accessory kit with the seal, fastening material and electrical plug connector.
Yes, it can be mounted vertically or horizontally. The unit measures 35.30 in (897 mm) H x 11.97 in (304 mm) W x 16.04 in (407 mm) D, with louvers extending 1.5 in on either side.
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021
Hammond Manufacturing · 012000055