The FLHTF125A115 is a fan-forced enclosure heater with a built-in thermostat, rated 125 W on 120 V, 60 Hz and moving 20 CFM. It is designed to prevent condensation or maintain a minimum temperature inside a control panel or metal enclosure, protecting critical components from freezing and condensation. It is not intended as a comfort or space heater.
The housing measures 5.5" x 4.0" x 5.3" (H x W x D) in the ordering table, with 139.07 mm [5.475 in] x 101.60 mm [4.000 in] x 133.86 mm [5.270 in] shown on the part drawing. The drawing lists UL Recognized to UL 508A and CSA Standard C22.2 No. 88 approvals, under UL File E331157.
The outer casing is aluminum alloy. The adjustable thermostat covers -18 C to +38 C (0 F to +100 F), and a Fan Auto/On switch with pilot light shows when heat is on. In FAN mode the fan runs continuously for more uniform temperature distribution and heat is still provided below the set point; in AUTO mode the fan cycles on only when the heating element is energized. An automatic reset temperature limit switch breaks power to the element on fan failure or overheat.
Mount the FLHTF125A115 vertically inside a metal enclosure on a metal surface, terminal block at the bottom and discharge vents at the top, using four #10 metal screws, as low and central as possible. Keep heat-sensitive components clear of the vents by the FLHTF125 clearances (4in / 100mm X, 1in / 25mm Y). Wiring is by qualified personnel with wire rated at least 90°C; there is no OFF position, so disconnect supply power to shut it down.
| Description | 125W Heater, 115V w/Tstat |
| Product Type | Fan-forced enclosure heater with thermostat (FLH Series) |
| Short Description | ENCLOSURE HEATER 125W, 120VAC |
| Drawing Depth | 133.86 mm [5.270 in] |
| Drawing Width | 101.60 mm [4.000 in] |
| Drawing Height | 139.07 mm [5.475 in] |
| Overall Dimensions (H X W X D) | 5.5" x 4.0" x 5.3" |
| Watts | 125 W |
| Wiring | Wires rated no less than 90°C; wired by qualified personnel to local electrical code; connect to a grounded source only |
| Voltage | 120 V |
| Frequency | 60 Hz |
| Connection | Terminal block |
| Power Switch | No OFF position; disconnect supply power to shut down |
| Drawing Rating | 120 VAC, 60 Hz, 125 W |
| UPC | 623980402888 |
| UNSPSC | 40101819 |
| Airflow | 20 CFM |
| Fan Modes | FAN (continuous) / AUTO (fan runs only when heating element is energized) |
| Heat Indicator | Pilot light for Heat On indication |
| Thermostat Range | -18 C to +38 C (0 F to +100 F) |
| Fan Motor Bearings | Permanently lubricated |
| Overheat Protection | Automatic reset temperature limit switch (TCO disc) opens on overheat or fan failure |
| Location | Centre of the enclosure, as low as possible |
| Mounting | Inside a metal enclosure on a metal surface, vertical position, terminal block at bottom and discharge vents at top |
| Fasteners | Four #10 metal screws |
| Clearance To Heat-Sensitive Components | X: 4in / 100mm; Y: 1in / 25mm |
| Included | Operation and Installation Instruction sheet |
| Shipping Weight | 2.5 lbs (1.13 kg) |
| Housing | Aluminum alloy |
| Environment | Interior use, dry locations; not for hazardous, corrosive, dusty or wet environments |
| Storage Temperature | -30°C to +100°C (-22°F to 212°F) |
| Operating Temperature | -20°C to +70°C (-4°F to 158°F) |
| Approvals | UL Recognized Standard UL 508A; CSA Standard C22.2 No. 88 |
| UL File # | E331157 |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
| Series Certification | cULus Recognized to UL 508A & C22.2 No. 14-13 (Category NITW2 / NITW8); CSA Certified to C22.2 No. 88:19 (Class 2871-02) |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
It is rated 125 W at 120 V, 60 Hz. The drawing rating reads 120 VAC, 60 Hz, 125 W.
Yes. The adjustable thermostat is built in and covers -18 C to +38 C (0 F to +100 F).
Vertically inside a metal enclosure on a metal surface, terminal block at the bottom, using four #10 metal screws. Keep heat-sensitive components at least 4in / 100mm (X) and 1in / 25mm (Y) from the discharge vents.
No. The heater does not have an OFF position; power must be disconnected from the supply to fully shut it down. The Fan Auto/On switch only selects whether the fan runs continuously or cycles with the heating element.
An automatic reset temperature limit switch opens on fan failure or overheat, disconnecting power to the heating element until the enclosure temperature drops below the limit.
The drawing lists UL Recognized to UL 508A and CSA Standard C22.2 No. 88. UL File # E331157.
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021