
The DTS3265A460N3LG is a 9-12000 BTU/H side-mount outdoor air conditioner, the high-capacity light gray model in this DTS range with a Type 3R, 4 rating. It is built for large control and electrical enclosures where substantial heat must be removed through a closed loop, serving OEMs, integrators and facilities teams.
Clean enclosure air is recirculated in a closed loop and never mixes with contaminated ambient air, while the wide spacing between warm inlet and cold outlet reduces hot spots. The condenser has 3 mm fin spacing for protection against strongly contaminated and aggressive ambient air, so the unit runs filterless. It uses R134a refrigerant with a 1200 g charge, a hot gas bypass valve against evaporator freeze-up, and a built-in condensate evaporator. The exterior case is galvanized sheet steel finished in RAL7035 Light Gray; an ANSI 61 Gray version is ordered by replacing LG with GY in the part number.
For panels fed at 460 V, the DTS3265A460N3LG is rated 460 V 50/60 Hz and runs within 360-506 V. It draws only 3.14 A running (8 A starting) and consumes 1700 W; power connects at a terminal block. Rated cooling capacity is 12000 BTU (3500 W) at +95/+95F (+35/+35C), and the noise level is <70 dB(A). Listed dimensions are A 53.00 in (1346 mm), B 16.00 in (406 mm) and C 14.40 in (366 mm); unit weight is 150 lbs/ 68 kg. The drawing shows overall dimensions of 53.13 in (1349.61 mm) by 16.00 in (406.40 mm) by 14.38 in (365.21 mm).
The unit mounts on the side of any enclosure surface, and the gasket, mounting kit, cutout and drilling template, condensate drain hose and clamp are included. Its thermostat is accessible from inside the enclosure and adjusts from +77 to +113°F (+25 to +45°C), factory set to +95°F/+35°C. Startup self-diagnostics, LED fault indication, EMI/RFI suppression meeting CE and a door contact provision for power-down when the door opens round out the controls. Standards are UL, cUL and CE with IP56; this part carries a Type 3R, 4 rating and is REACH and RoHS compliant.
| Diagnostics | Self-diagnostics on startup |
| Door Contact | Provision for door contact allowing power down when enclosure door is opened |
| Air Circulation | Continuous air circulation from high capacity fans |
| Fault Indication | LED light |
| Series | DTS Series |
| Mounting | Side mounting on any enclosure surface |
| Product Type | Outdoor air conditioner, side mounting |
| Long Description | Air Conditioner 9-12,000 BTU 460V |
| Cooling Principle | Closed loop; clean enclosure air recirculated without mixing with ambient air |
| Short Description | AC UNIT 9-12,000BTU/H 460V |
| Nominal Cooling Class | 9-12000 BTU/H |
| A | 53.00 in (1346 mm) |
| B | 16.00 in (406 mm) |
| C | 14.40 in (366 mm) |
| Unit Weight | 150 lbs/ 68 kg |
| Overall Depth (Drawing) | 14.38 in (365.21 mm) |
| Overall Width (Drawing) | 16.00 in (406.40 mm) |
| Overall Dimension (Drawing) | 53.13 in (1349.61 mm) |
| Line Cord | Terminal Block |
| Running Amps | 3.14 A |
| Rated Voltage | 460 V 50/60 Hz |
| Starting Current | 8 A |
| Power Consumption | 1700 W |
| Range Of Operation | 360-506 V |
| EMI/RFI Suppression | Meets CE |
| UPC | 623980720142 |
| UNSPSC | 40101701 |
| Part Number | DTS3265A460N3LG |
| Filter Mat | Filterless |
| Factory Setting | +95°F/+35°C |
| Freeze Protection | Hot gas bypass valve |
| Thermostat Access | Accessible from inside enclosure |
| Refrigerant Charge | 1200 g |
| Type Of Refrigerant | R134a |
| Condensate Discharge | Condensate Evaporator |
| Condenser Fin Spacing | 3 mm |
| Adjustable Control Range | +77..+113°F (+25..+45°C) |
| Cooling Capacity At +95/+95F (+35/+35C) | 12000 BTU (3500 W) |
| Air Capacity (Unrestricted), First Listed | Internal Circulation 706 CFM |
| Air Capacity (Unrestricted), Second Listed | Internal Circulation 706 CFM |
| Included | Gasket, mounting kit and template for enclosure cutout and drilling; condensate drain hose and clamp |
| Shipping Weight | 150 lbs (68.04 kg) |
| Available Accessories | Remote Door Switches, Filter Kits, Gasket Kits, Water Condensate Evaporator, Condensate Bottle |
| Finish | RAL7035 Light Gray |
| Exterior Case | Galvanized Sheet Steel |
| Alternate Finish | ANSI 61 Gray (replace LG with GY) |
| Noise Level | <70 dB(A) |
| Type Rating | 3R, 4 |
| Ingress Protection | IP56 |
| Max. Ambient Air Temp. | +131°F (+55°C) |
| Min. Ambient Air Temp. | +32°F (0°C) |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
It is rated 460 V 50/60 Hz with a range of operation of 360-506 V. Power consumption is 1700 W, running current 3.14 A and starting current 8 A; wiring connects to a terminal block.
The part is listed as a 9-12000 BTU/H unit, and the spec sheet rates cooling capacity at 12000 BTU (3500 W) at +95/+95F (+35/+35C).
Yes. The spec sheet states that for ANSI 61 Gray you replace LG with GY in the part number. The standard finish is RAL7035 Light Gray on galvanized sheet steel.
A gasket, mounting kit and template for the enclosure cutout and drilling are included, and a condensate drain hose and clamp are provided.
Maximum ambient air temperature is +131°F (+55°C) and minimum is +32°F (0°C). The thermostat adjusts from +77 to +113°F (+25 to +45°C), factory set at +95°F/+35°C.
The unit is listed as filterless. Its condenser uses 3 mm fin spacing for protection against strongly contaminated and aggressive ambient air; filter kits are offered as an accessory.
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021
Hammond Manufacturing · 012000055