The DTS3141A460LG brings 4,100 BTU/h (1,200 W) of side-mounted, closed-loop cooling to indoor NEMA 12 enclosures fed from 460 V 50/60 Hz industrial distribution, drawing just 2.25 A running. It is a fit for electricians and panel shops that want to power enclosure cooling directly from the same 460 V bus that feeds the equipment inside.
Designed for side mounting on any enclosure surface, the unit uses closed loop cooling so clean enclosure air is recirculated without ever mixing with contaminated ambient air, and it keeps maximum clearance between the warm inlet and cold outlet to reduce hot spots. The exterior case is galvanized steel with a powdercoat finish in RAL7035 light gray; an ANSI 61 gray version is available by replacing LG with GY. A hot gas bypass valve prevents evaporator freeze up while minimizing heavy inrush currents.
DTS3141A460LG is rated 460 V 50/60 Hz with an operating range of 360-506 V, consumes 1200 W, and draws 2.25 A running and 15 A starting, wired through a terminal block. It carries a 400 g charge of R134a refrigerant, moves 177 CFM internally and 100 CFM externally (unrestricted), and uses a 150 g/m² filter mat. The thermostat, accessible from inside the enclosure, adjusts from +77 to +113°F (+25 to +45°C) with a factory setting of +95°F (+35°C). Rated ambient range is +59°F (+15°C) to +131°F (+55°C), with a noise level of <70 dB(A).
Unit weight is 89 lbs (40 kg) and shipping weight is 95 lbs (43.09 kg). Gasket, mounting kit and template for the enclosure cutout and drilling are included, as are a condensate drain hose and clamp, and a built-in condensate evaporator handles condensate discharge. Self-diagnostics run on startup, faults are shown by LED, and a door contact provision allows power down when the enclosure door is opened. The series carries UL, cUL and CE approvals and maintains the enclosure's NEMA 12 (IP 54) rating. This part is listed as RoHS and REACH compliant.
| Thermostat | Accessible from inside enclosure |
| Diagnostics | Self-diagnostics on startup; fault indication via LED light |
| Door Contact | Provision for door contact allowing power down when enclosure door is opened |
| Included Items | Gasket, mounting kit and template for enclosure cutout and drilling; condensate drain hose and clamp |
| Mounting | Side mounting on any enclosure surface |
| Product Type | Side-mounting indoor enclosure air conditioner (DTS Series, 4000-7000 BTU/H, Type 12) |
| Short Description | AIR CONDIT 460V LG |
| Manufacturer Description | Air Conditioner 460V LG |
| Line Cord | Terminal Block |
| Running Amps | 2.25 A |
| Rated Voltage | 460 V 50/60 Hz |
| Starting Current | 15 A |
| Power Consumption | 1200 W |
| Range Of Operation | 360-506 V |
| EMI/RFI Suppression | Meets CE |
| Available Accessories | Remote Door Switches, Gasket Kits, Water Condensate Evaporator, Condensate Bottle |
| UPC | 623980010168 |
| UNSPSC | 40101701 |
| Part Number | DTS3141A460LG |
| Filter Mat | 150 g/m² |
| Noise Level | <70 dB(A) |
| Cooling Principle | Closed loop; enclosure air recirculated without mixing with ambient air |
| Refrigerant Charge | 400 g |
| Type Of Refrigerant | R134a |
| Condensate Discharge | Condensate Evaporator (built in) |
| Evaporator Protection | Hot gas bypass valve prevents evaporator freeze up while minimizing heavy inrush currents on large BTU/H units |
| Adjustable Control Range | +77..+113°F / +25..+45°C; factory setting +95°F/+35°C |
| Cooling Capacity (+95/+95°F, +35/+35°C) | 4100 BTU/h (1200 Watts) |
| Air Capacity, External Circulation (Unrestricted) | 100 CFM |
| Air Capacity, Internal Circulation (Unrestricted) | 177 CFM |
| Unit Weight | 89 lbs (40 kg) |
| Shipping Weight | 95 lbs (43.09 kg) |
| Finish | RAL7035 Light Gray |
| Exterior Case | Galvanized Steel Powdercoat finish |
| Alternate Finish | ANSI 61 Gray (replace LG with GY in the part number) |
| NEMA Rating | Enclosures IP 54 / Nema 12 |
| Series Rating | Maintains enclosure's NEMA 12 rating; IP 54 |
| Max. Ambient Air Temp | +131°F (+55°C) |
| Min. Ambient Air Temp | +59°F (+15°C) |
| RoHS Compliant | Yes |
| REACH Compliant | Yes |
Business account holders on Cooling Systems typically save 25% vs. retail pricing. Create a free account to see your price.
The spec sheet rates it at 4100 BTU/h (1200 W) at +95/+95°F (+35/+35°C).
It is rated 460 V 50/60 Hz with a range of operation of 360-506 V. Power consumption is 1200 W, running current 2.25 A and starting current 15 A, connected via terminal block.
This series is an indoor unit that maintains an enclosure's NEMA 12 (IP 54) rating, with an ambient range of +59°F (+15°C) to +131°F (+55°C). The data does not list an outdoor rating for it.
A gasket, mounting kit and template for the enclosure cutout and drilling are included, along with a condensate drain hose and clamp.
The unit has a built-in condensate evaporator for condensate discharge; a drain hose and clamp are also provided. A water condensate evaporator and condensate bottle are listed as accessories.
This part is RAL7035 light gray. For ANSI 61 gray, the spec sheet says to replace LG with GY in the part number.
Hammond Manufacturing · 010000018
Hammond Manufacturing · 012000019
Hammond Manufacturing · 012000020
Hammond Manufacturing · 012000021
Hammond Manufacturing · 012000055